MEDC HD1 Range
  

·         Zone 0, Zone 1 and Zone 2 use

·         ATEX certified
EExd IIB T3/T6
Exd IIC T6
EExem II T4/T6
Ex ia IIC T4/T6

·         IECEx certified
Ex ia IIC T4/T6 Ga

·         UL listed for USA and Canada:
Class I, Div 2, Groups A, B, C D

·         TR CU certified

·         CQST certified

·         CCOE certified

·         SIL 2 certified

·         IP66 & IP67

·         Certified temperature:
–20ºC to +125ºC (Exd)*
–20ºC to +55ºC (Exem/UL)
–55ºC to +55ºC (Exia)

·         Stainless steel probe

·         Detector temperature settings:
60ºC to 385ºC, (140ºF to 725ºF)

·         Marine grade alloy or GRP
enclosure

·         Optional stainless steel guard

·         *Model dependent

 
Request for quotation

Description

The Eaton heat detector has been designed for use in hazardous environments. These units are suitable for fire alarm and/or suppression systems in offshore and onshore applications including paint spray booths, flammable material stores, turbine rooms, extract ductwork and other hazardous areas throughout the oil & gas, petrochemical and process industries.

Comprising a Fenwal rate-compensated detector with all-stainless steel external construction, mounted to either a type SM87 marine grade alloy enclosure (Exd version) or JB10 corrosion-free GRP enclosure (Ex ia, Ex em/UL versions). The contact in the detector CLOSES at alarm temperature.

To select appropriate temperature setting see specification on reverse.

Datasheet MEDC HD1 Range

Download the datasheet below.

 HD1 heat detector

 HD1 UL heat detector

Related products